Thursday, May 8, 2008

Fluorescent lamps

Fluorescent lamps are low pressure gas discharge lamps in which the invisible UV radiation generated by the discharge is converted into visible radiation (i.e. light) with the aid of phosphors. (Principle of fluorescence) There are tubular, ring-shaped and U-shaped fluorescent lamps and also compact fluorescent lamps. The tube diameter is often expressed in eighths of an inch (e.g. T5 = 5/8'' = 16 mm). In the lamp catalogues, diameters are also given in millimetres (e.g. 16 mm for T5 lamps). Most lamps are internationally standardized. Like all discharge lamps, fluorescent lamps cannot be operated directly on mains voltage because of their negative internal resistance characteristics. Suitable control gear between the mains supply and the lamp, limits and control the lamp current and ensures reliable starting under specific conditions. Fluorescent lamps have various operating modes, depending on the way in which the electrodes are brought up to the temperature:
Current-controlled preheating in switch-start mode, preferred in countries with a high mains voltage (200 V or more). Used in most electronic control gear (ECG).
Voltage-controlled preheating with additional transformer for "rapid start" mode.
No preheating (cold start, used for example with slimline lamps). This type of starting reduces the lamp life more than any other type and is therefore not recommended for systems with frequent on/off switching.
Electronic control gear (ECG) converts the mains frequency into a high frequency supply in the region of 35 to 50 kHz. As a result, the 100 Hz flicker that may appear as a stroboscopic effect, for example with rotating machines, is much less noticeable or virtually eliminated. Another advantage of ECG operation is the additional energy savings of around 25% for the same luminous flux, comprising:
10% high luminous efficacy from the fluorescent lamp operating at a high frequency
Much lower losses in the ECG (less than half) compared with conventional control gear (CCG) Dimming Dimmable ECGs make use of the property of a choke whereby its inductance increases as the frequency increases. As the operating frequency is made to increase, the choke connected in series with the lamp supplies a progressively lower current. The frequency is controlled via a 1-10 V or a DALI interface. The dimmable ECGs must also ensure that in the dimmed state the cathodes are constantly heated so that they continue to emit electrons even when the lamp current is at a low level. Lamp life and resistance to switching transients If fluorescent lamps are operated with CCGs and conventional starters their life is shortened considerably as the frequency of on/off switching increases. The same phenomenon can be observed with cold-start ECGs, which have the ability of starting fluorescent lamps instantly. However, the rapid transition from glow discharge temperature to emission temperature seriously damages the cathodes, so frequent switching cycles reduce the life of fluorescent lamps. Warm start control gear behave in a completely different way. In this case, the cathodes are heated before ignition, which virtually eliminates switching damage to the cathodes. The associated delay in ignition, of around a second is not a serious inconvenience. Thermal behaviour The physical properties of fluorescent lamps depend on their ambient temperature. This in turn depends on the characteristic temperature sensitivity of the mercury vapour pressure in the lamp. At low temperatures it is too low so there are too few atoms that can be excited. At excessively high temperatures the high vapour pressure results increasingly in self-absorption of the generated UV radiation. The lamps achieve their maximum luminous output at an ambient temperature of approx. 25°C. In the case of T5 lamps with a tube diameter of 16mm (FH®, FQ®) the rated luminous flux is specified at 25°C, as with other fluorescent lamps but their maximum luminous flux is achieved at an ambient temperature of 33°C to 37°C. In other words, one advantage of T5 lamps is the higher light output from ‘hot’ compact luminaires.

Emergency lighting

There are two types of emergency lighting - standby lighting and safety lighting. Standby lighting takes over the functions of the normal lighting system if the power supply to that system fails so that essential work can continue. In most cases, standby power generators are used and these then supply power to the normal luminaires. The generators must guarantee at least 10% of the illuminance recommended for the activity. There are three types of safety lighting:
Safety lighting for escape routes; safe evacuation calls for a minimum illuminance of >1 lx at a height of 0.2 m, with a uniformity ratio of 1:40.
Escape lighting as minimum background lighting to enable people to reach emergency exits in large rooms.
Safety lighting for hazardous workplaces (near machines with moving parts) if failure of the normal lighting system presents an immediate risk of an accident or injury.

Monday, May 5, 2008

Disposal of old lamps

Disposal of old lamps and electronic control gear
Disposal of incandescent lampsIncandescent lamps consist of glass and metal. They do not contain any materials that will harm the environment so they can be simply thrown away with the household refuse. They should not be placed in containers for recycled glass, however, because the glass used for these lamps is not the same as the glass used for bottles. Tungsten-halogen lamps contain very small quantities of halogens and halogen-hydrogen compounds, but the amounts are insignificant (only a few millionths of a gram). Even several lamps together do not present any risk to people or the environment. The lamps can therefore be thrown away with household waste.Disposal of discharge lampsFluorescent tubes, compact fluorescent lamps, high pressure mercury, sodium and metal halide lamps all contain small quantities of mercury.These lamps can be recycled and the mercury recovered, but they can also be disposed of to special land-fill sites for mercury containing waste (seek advice from the Environment department of the local authority)Electronic control gearECGs do not contain any material that will harm the environment but they do contain recycable electronic components so they should be disposed of as electronic waste.

Dimming lighting system

Dimmable lighting systems were developed originally to meet the need for lighting that was easier on the eye. To an increasing extent, these systems are now also being used for cost saving reasons. Users can control the lighting with remote controls and switches, or control circuits with daylight sensors can be used. Leading edge phase dimming is used for low voltage tungsten halogen lamps operated with magnetic transformers. Trailing edge phase dimming is generally used for those lamps operated with electronic transformers. Compact fluorescent lamps (dimming range 3% to 100%) and fluorescent tubes (dimming range 1% to 100%) with electronic control gear are dimmed via a 1-10 V interface. Cables can either be laid separately (recommended for cable lengths > 100 m) or together, provided the requirements of wiring regulations are met.

DALI (Digital Adressable Lighting Interface)

DALI is a method of controlling electronic control gear for fluorescent lamps using digital signals. Unlike analogue brightness controls, DALI enables each luminaire to be controlled individually. It can be easily integrated in a building management system. Individual addressing means that not only the luminaires can be controlled but they can provide feedback messages so they can be operated in versatile energy-saving arrangements. DALI supplements Appendix E of the existing IEC Standard 929 in terms of the mode of operation of electronic control gear
1. Digital switching - Luminaires can be switched via the control cables irrespective of polarity.
2. Addressing - 64 ballasts can be addressed, allowing them to be controlled independently with a common control wire.
3. Simple control wiring - Switching and dimming circuits are independent of the wiring layout, allowing maximum flexibility and convenience; this low-voltage wire can be routed in any way and is polarity-free to reduce installation errors.
4. Refurbishment - Control circuits are independent of polarity. This allows the use of existing wiring in old buildings. In new buildings, a five-conductor cable for both power supply and control wiring can be employed.
5. Lighting scenes - Preset lighting scenes for different tasks and moods can be programmed and stored in the DALI ballasts.
6. Flexible room layout - Future layout changes do not necessitate wiring changes.
7. Upgrading - New sensors or interfaces can be added without changing the luminaire wiring; simply choose which luminaires are to be controlled and reprogrammed.
8. Distortion-free - Digital signals allow greater freedom in wiring layout.
9. Flexible - Each sensor can be configured to control any luminaire or group of luminaires.
10. Overlapping groups - Luminaires can be included in more than one sensor group, e.g. movement detection and infrared control.
11. 11 Infrared control zone 1 - Zones can be altered without the need to rewire.
12. Infrared control zone 2
13 PIR (passive infrared) controlled zone
14. Daylight regulating zone - Controlled by Photocell
15. DALI room controller

Control gear for fluorescent lamps

Discharge lamps have to be operated with control gear to limit the current. There is a choice of conventional, low-loss or electronic control gear. An important factor as far as quality is concerned is their power loss which, together with the lamp wattage, is used to calculate the system wattage.Electronic control gear (ECG) In contrast to conventional control gear, ECGs operate at frequencies at or above 30 kHz which means they offer significant gains in efficiency. These gains are based essentially on two mechanisms:
A reduction in electrode losses.
An increase in luminous efficacy, which is due almost entirely to more efficient conversion of electrical energy into the UV lines of the mercury atom at 185 nm and 254 nm.The use of modern ECGs, above all for fluorescent lamps, has led to significant increases in lighting comfort, economy and reliability.
Lighting comfort
Flicker-free starting
Pleasant flicker-free light with no stroboscopic effects
Silent operation with no annoying hum from chokes
No flashing of faulty lamps
Automatic restart of replacement lamps
Economy
Up to 30% savings in power input compared with CCG operation
More than 50% longer lamp life compared with CCG/LLG thanks to preheat start
Low maintenance costs
Suitable for use in emergency lighting systems to VDE 0108
Reduction in energy costs for air-conditioning systems
Reliability
Safe shutdown of defective lamps
Compliance with the specific standards for safety and EMC
Protective circuit to guard against transient voltage surges and prolonged overvoltages
Dimmable electronic control gear enables compact fluorescent lamps to be dimmed smoothly and without flicker from 100% to 3% luminous flux and tubular fluorescent lamps from 100 % to 1% luminous flux. Control is via a separate 1-10 V interface or a digital addressable lighting interface (DALI).
Conventional control gear (CCG):
This is a simple self-inductance comprising an iron core around which copper wire is wound. Because of its ohmic resistance there is considerable power losses and from self heating. The system wattage for a 26W compact fluorescent lamp operated with conventional control gear is 32 W; in other words, the power loss is 6 W (23%). By contrast, the system wattage with an ECG is 28 W, which corresponds to a power loss of only 7.5%. The various operating modes are as follows:
Switch-start operation
Starter less operation
Control gear with temperature limitation
Switch-start operation can be described as follows:
The voltage needed for the starter to generate a glow discharge between the bimetallic contacts, is lower than the ignition voltage of the lamp with cold cathodes. When mains voltage is applied, the starter generates a glow discharge, the current of which heats up the cathodes. The bimetallic contacts then close and the full short-circuit current of the choke flows through the cathodes of the lamp. As the bimetallic contacts cool down they spring open again. A high voltage pulse is generated by the choke to ignite the lamp. Once the lamp has ignited only the lamp voltage is across the starter. This voltage is too low to cause the starter to initiate a glow discharge, so does not attempt to light the lamp.Special lamps are needed for starter-less operation. Whereas fluorescent lamps connected to a European 230-240 V mains can be operated with simple chokes and an additional preheating transformer or a sophisticated double resonance choke is needed for starter-less operation. The voltage for lamps connected to American 120 V supply systems has to be transformed with two additional heater windings on the control transformer, which involves little extra outlay. For this reason, starter-less circuits are widespread in the USA. Control gear with temperature limitation help ensure that dangerous overheating does not occur as lamps reach the end of their lives. This protection is provided by thermal cut-outs approved in VDE 0712 T10 The European Ballast Directive (2000/55/EC) has classified all fluorescent ballasts in terms of their energy efficiency. The most inefficient types will be legally banned from sale in Europe from May 2002. The aim of the Directive is to encourage the widespread use of electronic control gear which are the best in terms of energy efficiency. Low-loss gear (LLG): Compared to conventional control gear, low-loss gear has a lower power loss but are larger and are more costly to manufacture because of their improved design and larger iron cores. The system wattage for a 26 W compact fluorescent lamp, for example, is around 30 W

Constant light control

This is incorporated into dimmable lighting installations with the aim of reducing lighting costs, increasing lighting comfort and promoting individuality.This form of control is based on a dimmable ECG with a 1-10 V interface or DALI in combination with appropriate sensors. A distinction is made between automatic controllers, manual controllers and complex controllers. The choice of appropriate 1-10V dimmer components depends to a large extent on the application.The lighting system is controlled by light sensors according to the amount of available daylight, so full use is made of free natural sunlight. Energy savings of up to 60% are possible, rising to 70% if motion detectors, time switches and sensors with automatic disconnection circuits are used.

Computer workstations

Guidelines for lighting at computer workstations are given in DIN 5035, Part 2 and EU Directive 90/270/EWG. Its appendix contains the following minimum requirements:Lighting
General lighting and/or special lighting (task lamps) must be dimensioned and arranged so that lighting conditions are satisfactory and contrast between the screen and its surroundings is adequate, according to the type of activity and the viewing requirements of the user.
Glare, reflex or reflections on the screen or any reflective surface must be avoided by arranging the objects in the work area according to the arrangement and technical properties of the artificial light sources. Reflex and glare
Computer workstations must be set up so that light sources such as windows, other openings, transparent or translucent partitions, bright items of furniture and light coloured walls do not produce reflections on the screen.
Windows have to be equipped with suitable adjustable mechanisms for preventing or reducing the amount of daylight falling on the workplace. For further technical information see the DIN 5035-7 and DIN 66234-7 standards.

Common Lamp bases (Conforming to IEC 60061)


Bases for GLS lamps(Dimensions in mm)

Bases for tungsten-halogen lamps(Dimensions in mm)

Bases for compact fluorescent lamps (for switch-start operation)(Dimensions in mm)


Bases for compact fluorescent lamps (for high frequency operation)(Dimensions in mm)


Bases for compact fluorescent lamps (for high frequency operation)(Dimensions in mm)




Bases for tubular fluorescent lamps(Dimensions in mm)

Bases for discharge lamps(Dimensions in mm)

Adaptation of Light

This is the ability of the eye to adjust to changes in luminance by making the pupil larger or smaller. It means we can see correctly across a wide range of illuminance values. The time taken to adapt in this way is largely determined by the luminances at the start and end of the adaptation process. This adaptation takes place very quickly from dark to light (brightness adaptation) but much more slowly (30 minutes or more) from light to dark (darkness adaptation).

lamp designations

TC-S
Tube Compact-Single
TC-SEL
Tube Compact-Single Electronic
TC-D
Tube Compact-Double
TC-DEL
Tube Compact-Double Electronic
TC-T
Tube Compact-Triple
TC-TEL
Tube Compact-Triple Electronic
TC-Q
Tube Compact-Quad
TC-QEL
Tube Compact-Quad Electronic
TC-DD
Tube Compact-Double D-Shape
TC-L
Tube Compact-Long
TC-F
Tube Compact-Flat
T2 (T7)
Tube Ø 2/8" (7 mm)
T5 (T16)
Tube Ø 5/8" (16 mm)
T8 (T26)
Tube Ø 8/8" (26 mm)
T12 (T38)
Tube Ø 12/8" (38 mm)
T-U
Tube U-Shape
T-R
Tube Ring-Shape
T-R5 (T-R16)
Tube Ring-Shape Ø 5/8" (16 mm)

Explanation of the IP numbers

Explanation of the IP numbers for the degree of protection in accordance with DIN IEC 598/VDE 0711
Number
1st number

Brief description
Brief explanation of which foreign bodies must not be allowed to penetrate into the casing
2nd number

Brief description
Details on the protection to be provided by the casing
IP20
1st number
2
Protected from solid foreign bodies
Fingers and the like up to 80 mm long. Foreign bodies greater than 12 mm dia.
2nd number
0
Unprotected
No special protection.
IP...1
2nd number
1
Protected from water droplets
Water droplets (droplets falling vertically) do not cause any damage.
IP...3
2nd number
3
Protected from water splashes
Water spray from an angle of up to 60° from the vertical must not cause any damage.
IP...4
2nd number
4
Protected from water splashes
Water splashes from any direction must not cause any damage.
IP...5
2nd number
5
Protected from water jets
Water jets from any direction must not cause any damage.
IP...7
2nd number
7
Watertight (immersible)
No water in dangerous quantities may penetrate when immersed in water in the given conditions in terms of pressure and time.
IP...8
2nd number
8
Tight to pressurized water (under water)
The equipment is suitable for continuous operation under water in the conditions stated by the manufacturer.
IP4...
1st number
4
Protection from foreign bodies greater than 1 mm
Wires or strips thicker than 1 mm. Foreign bodies greater than 1 mm dia.
IP5...
1st number
5
Dust-protected
Dust penetration is not completely prevented but dust does not penetrate in quantities which inhibit proper operation.
IP6...
1st number
6
Dust-tight
No dust penetration.

Sunday, May 4, 2008

Lampholders for compact fluorescent lamps




Vossloh-Schwabe produces the majority of lampholders for TC lamps using PBT, a thermoplastic material. This highly heat-resistant material is responsible for the T140 temperature rating. Leading lamp manufacturers also use PBT for the lamp bases they produce. This material harmonisation in conjunction with fatigue-free, stainless steel lamp mounting springs ensures a permanently secure lamp fit.
Lampholders for double-ended fluorescent lamps
VS lampholders for T lamps are characterised by a number of technical features that guarantee a high degree of reliability and safety. In the first instance, the large rotor, which is characteristic of the vast majority of these lampholders, acts as a heat shield. Made of extremely heat-resistant PBT, the rotor´s fatigue strength at elevated temperatures amounts to 140 °C. Thus shielded against the heat of the lamp base, these lampholders attract a temperature rating of T130. In addition, Vossloh-Schwabe produces another series of rotor-like push-through lampholders whose complete front plate is made of PBT and thus acts as a heat shield. These lampholders attract a temperature rating of T140.
The maximum permissible temperature at the lampholder rear of Tm 110 °C is applicable to all lampholder types. The second key feature of these lampholders is a highly effective lamp pin support that reliably prevents base pin deflection even on older lamps and guarantees a durable and firm contact.




Push-through lampholders
Push-through lampholders are inserted from below through a cut-out in the luminaire casing and are secured by lateral catches. This type of lampholder is frequently used in luminaires on which the lampholder remains visible from the outside, e.g. in so-called strip lighting. The electrical leads are laid beneath the sheet metal level. With push-through lampholders, the starter essentially determines the dimensions of the luminaire because it has to remain accessible from the outside and is thus positioned vertically in front of the lampholder.


Push-fit lampholders
This lampholder type, which is frequently found in surface-mounted ceiling and built-in luminaires, is pushed into the luminaire casing from above. The lampholder foot should protrude by no more than 4 mm to match the usual height of the spacing cams in the luminaire casing. These lampholders are mostly wired above the luminaire casing to the side of the lampholder. However, there are also lampholders on which the wiring runs through the lampholder foot, with the leads laid beneath the luminaire casing.







Built-in lampholders
This design is also predominantly used for recessed ceiling and surface-mounted luminaires. However, unlike push-fit lampholders, built-in lampholders are usually fitted at the ends of the luminaire boxes. In addition to the usual fixing with split pins attached to the rear, there are also countless versions with fixing clips, push-fit studs or screw-in holes, which are also available with spring-loaded length compensation. Built-in lampholders offer luminaire designers a wealth of scope regarding the choice of lamp position in relation to the reflector. This enables great variation in light distribution as the lampholder does not dictate the distance of the centre of the lamp from the metal casing.


Surface-mounting lampholders
The fastening system of surface-mounting lampholders usually consists of screws or rivets above a fixing level, along which the wiring is also laid. As this type of installation is usually too costly nowadays for large unit numbers, these lampholders are used almost exclusively for special applications, e.g. displays or illuminated advertisements.

Connecting terminals

In the interest of ensuring firm contacts and long component service life, Vossloh-Schwabe uses only top-quality materials for plastic or metal parts during the production of connection terminals. These quality features apply to both Vossloh-Schwabe´s luminaire connection terminals as well as to the terminals fitted to ballasts and lampholders.
Notes on connection terminals on electronic ballasts
Vossloh-Schwabe electronic ballasts are fitted with installation-friendly push-in connectors. In addition, many models for linear fluorescent lamps are also available with IDC terminals (for solid conductors, 0.5 mm²) and supplementary push-in terminals (for solid conductors, 0.5 -1.5 mm², stripped length 8+1mm or 7.5 - 8.5 mm). IDC terminals permit automated luminaire wiring and testing using the ALF system and are thus particularly efficient.
Notes on connection terminals on electromagnetic ballasts
Standard issue Vossloh-Schwabe electromagnetic ballasts are fitted with installation-friendly IDC/push-in terminals (combination terminals) or push-in terminals. The terminals are designed for use with solid conductors with cross-sections of 0.5 -1.0 mm² (combination terminals) or up to 1.5 mm² (push-in terminals) and are approved for current loads of up to 3 A (combination terminal) and 16 A (push-in terminal). The lead stripping length totals 8±1mm for push-in terminals; leads must not be stripped for IDC terminals.
On request, many ballasts can also be provided with screw terminals (current load up to 16 A) for conductor cross-sections of 0.5 to 2.5 mm².
Notes on connection terminals on lampholders
Vossloh-Schwabe usually equips lampholders for T and TC lamps as well as starter lampholders with installation-friendly push-in terminals for solid conductors of 0.5 -1.0 mm². Most lampholders are fitted with twin push-in terminals and thus permit through-wiring. The required lead stripping length amounts to 8+1mm for all types.





IDC terminals
In order to fully exploit the vast potential for rationalisation offered by automated wiring and testing with the ALF system, a totally new component family was developed that is equipped with the VDE-tested IDC terminal technology. This technology has already been used very successfully on a large scale in other branches of industry. This modification of the terminal geometry dispenses with the stripping of conductors that is required for the push-in, screw or crimping methods. This triedand-tested IDC terminal technology has created the foundation for efficient automation as it ensures high connection quality, rapid contacting as well as quality assurance. Components equipped in this fashion make it possible to through-wire several terminals with a single conductor. This constitutes a further economic advantage as it significantly reduces the required conductor lengths. Furthermore, this design principle makes it possible to use adapters to simply and reliably make electrical contact from above for a VDE-compatible final luminaire inspection.
Circuit diagrams for the operation of fluorescent lamps with electromagnetic ballasts




Inductive single circuit
Schaltungen für den Betrieb von Leuchtstofflampen mit KVGs

Inductive tandem circuit
Schaltungen für den Betrieb von Leuchtstofflampen mit KVGs




Parallel-compensated single circuit


Schaltungen für den Betrieb von Leuchtstofflampen mit KVGs

Parallel-compensated tandem circuit


Schaltungen für den Betrieb von Leuchtstofflampen mit KVGs




Parallel-compensated single circuit with high-reactance transformer




Parallel-compensated tandem circuit with high-reactance transformer

Electromagnetic ballasts

Electromagnetic (inductive) ballasts are active components that in conjunction with starters preheat the lamp electrodes, supply the ignition voltage and stabilise lamp currents during operation. Series or parallel capacitors are required to compensate blind current.
For installation in luminaires, consideration must be taken of the mains voltage and mains frequency, the dimensions and maximum thermal values as well as any potential noise generation. To fulfil these special requirements, Vossloh-Schwabe provides numerous ballasts with differing technical specifications.
Vossloh-Schwabe magnetic ballasts have been optimised with regard to their magnetic fields and loads so that they are usually unnoticeable. However, as magnetic vibrations can affect large areas depending on the luminaire design, this should be taken into consideration when designing luminaires. If necessary, beads or grooves should be fitted to prevent vibrations from spreading. The service life of an inductive ballast is determined by the material chosen for the winding insulation. The maximum winding temperature denotes the temperature (tw) that the insulation will withstand for a period of 10 years given continuous operation under rated conditions. This maximum winding temperature must not be exceeded in real conditions to ensure the ballast can achieve its full service life. The winding temperature of the ballast that is measured in the luminaire is made up of the ambient temperature of the luminaire, the thermal conditions within the luminaire and the power loss of the ballast. The Dt marking on the ballast type plate provides a measure of the power loss of the ballast. In addition to this, the power loss of ballast-lamp circuits is measured in accordance with EN 50294. This test method forms the basis for the CELMA energy classification of ballasts and is also applied in European Directive 2000/55/EC "Maximum Values Regulation of the Power Input of Fluorescent Lamp Circuits".

As a result of their design features, inductive ballasts cause leak current that is discharged via the earth conductor (potential connection) of the luminaire. The maximum permissible leak current for protection class luminaires is 1mA, a value of which all Vossloh-Schwabe electronic ballasts fall clearly short. Values of max. 0.1 mA are measured per electromagnetic ballast. However, as these values accumulate with the number of installed ballasts, this should be taken into account when dimensioning the F1 protective switch.
Starters for fluorescent lamps
As mentioned above, the operation of fluorescent lamps also requires starters in addition to ballasts. A distinction is made between glow starters, which are also available with automatic cut-outs, and electronic starters. The correct choice of voltage and power range is crucial. Starters are available for 220 - 240 V and for 110 -127 V mains voltage. The latter are also required for twin-lamp operation (e.g. 2x18 W at 230 V). Operating the VS ballast SL (100 -127 V) depends on the use of a 220 - 240 V starter as these operating devices are high-reactance transformers that supply higher voltages to the lamp.

Circuit diagrams for the operation of fluorescent lamps with electronic ballasts

Circuit diagrams for the operation of tubular fluorescent lamp




Circuit diagrams for the operation of compact fluorescent lamps






Electronic ballasts (EB)

Ballasts for fluorescent lamps
The operation of a fluorescent lamp depends on a ballast that stabilises the lamp´s preheat current after connection to the mains and, in conjunction with the starter, also supplies the required lamp ignition voltage after preheating. After lamp ignition, the ballast then serves to limit the lamp current. As fluorescent lamps are characterised by a negative characteristic current-voltage curve, lamp current stabilisation is extremely important with regard to both the lamp´s stable operation and its service life. In addition to this, a lamp´s service life is critically dependent on compliance with the starting conditions (preheat current and ignition voltage). Unfavourable starting conditions cause damage to the electrodes every time the lamp is started and thus reduce the lamp´s service life. Furthermore, care should be taken to prevent cross-discharge in the electrode area during preheating, which also shortens lamp service life.
Ballasts are available in electromagnetic or electronic form. Electromagnetic (inductive) ballasts have to be operated in conjunction with starters for lamp ignition and capacitors for blind current compensation. In addition, capacitors for RFI suppression will also be required for certain circuits. Electronic ballasts can be operated without any additional components.
Electronic ballasts (EB)
VS electronic ballasts are designed for mains voltages of 220 V to 240 V and are used to operate fluorescent lamps at high frequency (20 - 50 kHz). The lamps are ignited with an internally generated ignition voltage, thereby removing the need for an external starter. The power factor (l) > 0.95 also removes the need for compensation, unlike with electromagnetic ballasts. The only exceptions are low-output ELXs models, which attain a power factor of 0.6. Luminaires fitted with electronic ballasts are characterised by low energy consumption as they have substantially lower system power than conventional, inductive applications. This is firstly because the lamp consumes less power to achieve the same luminous flux and secondly the internal loss of an electronic ballast only amounts to approx. 8 % to 10 % of the lamp´s output. Furthermore, thanks to their modern circuitry, the power input of VS electronic ballasts remains constant even in the event of mains voltage fluctuations, thus ensuring permanently low energy consumption.
Vossloh-Schwabe electronic ballasts permit a broad range of applications. For instance, VosslohSchwabe´s product range includes many ballast types for multiple lamp operation. These ballasts reduce installation and component costs and thus enable particularly efficient luminaires. Twin-lamp electronic ballasts permit so-called master-slave operation. The lamps of two single-lamp luminaires are operated by a twin-lamp electronic ballast that is built into the so-called master luminaire. The lamp of the slave luminaire is electrically connected to the electronic ballast.
The use of electronic ballasts makes a lighting system both more convenient and efficient to operate:
reduced power consumption (up to 30 %) at undiminished light output
50 % longer service life
stabilised lamp output
overvoltage protection
no stroboscopic effect
flicker-free lamp start
no need for a starter or capacitor
low wiring effort
no radiated electromagnetic interference
low self-heating due to minimal power loss
automatic shutdown of defective lamps
automatic restart once the lamp has been changed
Vossloh-Schwabe electronic ballasts are developed on the basis of the latest technological and component standards and are produced using state-of-the-art technology, whereby consideration is taken of our customers´ quality standards in our quality assurance system.

Vossloh-Schwabe provides the respective electronic ballast family for the most diverse applications:
ELXs ballasts (warm start)
The family of ELXs ballasts forms a perfect alternative to magnetic ballasts. ELXs ballasts have the same fastening hole spacing as standard electromagnetic ballasts. The lamp is ignited after a preheating time (warm start) of 1.5 seconds. These ballasts are available for system outputs (lamp output plus power loss of the electronic ballast) of up to 25 W. The power factor of these ballasts amounts to approx. 0.6. The average service life of these ballasts totals 30,000 hours with a failure rate of ≤ 0.2 % per 1,000 operating hours.
ELXe ballasts (instant start)
With this ballast family, the lamps ignite immediately after connection to the mains voltage by applying an ignition voltage of max. 1,500 V to the gas discharge path of the lamp. The ignition time totals less than 0.2 seconds. As this puts a severe strain on the electrodes, the realistic number of lamp starts is limited to approx. 10,000 ignitions up to the end of the lamp¢¥s service life. For that reason, ELXe ballasts should only be used for applications demanding fewer than five lamp ignitions per day (e.g. in production sites, warehouses or department stores). As there is no need for preheating, ELXe ballasts only require one connection per electrode for lamp operation. This makes them suitable for use in explosion protected luminaires. In addition to this, they are extremely energy efficient as no lamp electrode losses occur. The average service life of these ballasts totals 50,000 hours with a failure rate of ≤ 0.2 % per 1,000 operating hours.
ELXc ballasts (warm start)
ELXc ballasts ensure the lamp is started following a defined lamp electrode preheating period of approx. 1.5 seconds using a fixed ignition voltage. This particularly gentle lamp start makes over 20,000 lamp starts possible. ELXc ballasts should be used for applications with high switching frequencies (e.g. hotels or offices) where energy savings as well as low maintenance costs are desired. The average service life of these ballasts totals 50,000 hours with a failure rate of ≤ 0.2 % per 1,000 operating hours.
ELXd ballasts (dimmable)
These are ELXc ballasts with an additional dimming function that is controlled via an interface fitted to the ballast. The interface of these ballasts can be either analogue (1-10 Volt) or digital (DALI; PUSH); the interface enables lighting to be ideally adjusted to suit the given need. Control components can also be used as long as they comply with the respective standard (appendix to IEC/EN 60929). When using ELXd ballasts in a lighting system, an energy saving of 75 % can be achieved if the control inputs of the ballasts are coupled with movement detectors and light sensors. The average service life of these ballasts totals 50,000 hours with a failure rate of ≤ 0.2 % per 1,000 operating hours.
To guarantee trouble-free operation and a long service life of the various types of electronic ballast, attention should be paid to the regulations and mounting instructions. In addition, the installation instructions for lighting systems must be observed when installing luminaires with electronic ballasts.